1-800-633-0405For the latest prices, please check AutomationDirect.com.Enclosure CoolingYou need to cool downHeat inside an enclosure can decrease the life expectancy of controlling units such as your PLC, HMI, AC drives and other items. Excessive heatcan cause nuisance faults from your electrical and electronic components: for example, overloads tripping unexpectedly. Heat will also changethe expected performance of circuit breakers and fuses, which can cause whole systems to shut down unexpectedly. So, if you have any electronicequipment or other heat sensitive devices, you may need cooling.What causes all that heat?There are basically two sources that can cause the enclosure’s internal temperature to rise above the ratings of the control equipment.Internal SourcesExternal SourcesThe same items that can be damaged by heat may alsobe the source of the heat. These include items such as: Power supplies Servos AC Drives/inverters Soft starters Transformers PLC systems Communication products HMI systems Battery back-up systemsOther sources of heat that can cause the internaltemperature of your enclosure to rise above a desiredlevel involve the external environment. These includeitems such as: Industrial ovens Solar heat gain Foundry equipment Blast furnacesGet the heat outHow do you get the heat out of your enclosure and away from those critical components?There are several basic cooling methods available, depending on the coolingrequirements and the enclosure environment.Radiation and Natural Convection CoolingNatural Convection CoolingHOTIf the ambient temperature outside the enclosure is cooler than the inside of the enclosure,some heat will be radiated into the atmosphere from the surface of the enclosure. Inenvironments where dust and water intrusion is not a concern, louvers can be added toallow outside air to flow through the enclosure via natural convection - the movementof air due to it's expansion (reduced density) when it's heated and contraction (increaseddensity) when it cools.On a large scale, natural convection can be a powerful force - it's one of the primarydrivers of our weather. But on the scale of an electrical enclosure, its cooling capacityis very limited. For larger heat loads, a more powerful cooling system may be needed.Since they create openings in the enclosure, louvers are typically limited to NEMA 1 and/or NEMA 3R applications. However, some louvers have optional filters that can be addedto maintain NEMA 12 protection.Forced Convection CoolingHOTForced Convection CoolingThe next step up from natural convection is forced convection cooling. The basiccooling mechanism is the same: cooler air from outside the enclosure passes throughthe enclosure to remove the heat. The difference is that the air is mechanically forcedthrough the enclosure by a filter fan. The fan produces higher air flow rates than naturalconvection, which in turn increases the amount of heat removed.As with natural convection cooling, the ambient air temperature must be lower than thedesired enclosure temperature for forced convection to be effective.COLDHOTA typical forced convection system consists of a fan and a grille, with a filter on the intakedevice and either a filter or louvers on the exhaust device. The filters and louvers allowthe enclosure to maintain NEMA 12 protection. In NEMA 4 or NEMA 4X environments,hoods can be added to both the fan and the grille to prevent the ingress of water.www.automationdirect.comEnclosures Thermal ManagementtENC-368

1-800-633-0405For the latest prices, please check AutomationDirect.com.Enclosure CoolingClosed Loop CoolingIf the environment is harsh, with heavy dust and debris or the presence of airbornechemicals, or there are wash-down requirements, the cooling system must be able tokeep the ambient air separate from the air inside the enclosure.Closed loop systems, which include heat exchangers and air conditioners, circulate theinternal air and ambient air through separate chambers connected by a refrigerationsystem that transfers heat from the internal air stream to the external air stream. Heatexchangers and air conditioners are both closed loop cooling systems. The primarydifference in the two is the refrigeration system.The refrigeration system in a heat exchanger is a set of sealed tubes of alcohol. Heatabsorbed from the internal enclosure air boils the liquid alcohol at the bottom of the tube,causing it to rise to the top. The heat is then rejected to the cooler ambient air stream,causing the alcohol to condense back to a liquid and fall to the bottom.Air Conditioners & Heat ExchangersCOLDHOTHeat exchangers are very efficient because the refrigeration system has no moving parts- the only moving parts are the two fans. But for the heat to transfer through the system,the ambient air must be colder than the air inside the enclosure, just as it must be forfilter fans.Enclosure air conditioners function in the same manner as a residential or automotiveair conditioner, with refrigeration loop powered by a compressor. The refrigerant absorbsheat from the internal air at the evaporator coil and rejects it to the ambient air at thecondenser coil. Unlike heat exchangers, they can provide cooling even if the ambienttemperature is higher than the enclosure temperature. They can also be scaled to handlelarger heat loads than any other cooling system.Enclosure air conditioners are available for NEMA 12, NEMA 4 and NEMA 4Xapplications.Vortex CoolersVortex coolers create a stream of extremely cold air from a supply of filtered compressedair. The cold air is injected into the enclosure, displacing warm air which is exhaustedback through the vortex cooler. While not a closed-loop system, they can be used in thesame harsh environments since the cold air injected into the enclosure is filtered air froma compressed air system, not ambient air. Vortex coolers can also be used where theambient temperature is higher than the enclosure temperature.Vortex CoolingCompressedAir InInternalAir OutRelief Valves toVent Hot AirInternalAir InSolenoidValveFilter/RegulatorInternalAir InCold EndMufflerSince vortex coolers prevent the ingress of ambient air or sprayed water and are madefrom corrosion-resistant materials, they can be used on NEMA 4X enclosures in harsh,wash-down, and/or corrosive environments.AdjustableThermostatClean ColdAir InsideVortex coolers are commonly used in lieu of a small or medium enclosure air conditionerin applications where there isn’t adequate space to mount an air conditioner, providedthere is an adequate supply of compressed air.Thermoelectric CoolersAnother alternative to a conventional air conditioner is a thermoelectric cooler, whichis sometimes referred to as a Peltier cooler. They function in a manner similar to an airconditioner or heat exchanger, with fans inside and outside the enclosure, but with athermoelectric unit replacing the fluid-based refrigeration system.The thermoelectric units consist of an array of semiconductors sandwiched between twoceramic plates. When a DC current is applied to the semiconductor array, heat is drivenfrom one plate to the other, creating a cold side and a warm side. This is known as thePeltier Effect. Fans circulate air across each of the plates, allowing the cold plate toabsorb heat from the enclosure and the warm plate to reject it to the ambient air.Like vortex coolers, thermoelectric coolers can be used with NEMA 4X enclosures inharsh, wash-down, and corrosive environments, and where the ambient temperatureexceeds the enclosure temperature.Thermoelectric CoolingAmbientAir OutInternalAir OutInternalAir InAmbientAir InInternalAir OutAmbientAir OutThermoelectric coolers are an alternative to air conditioners in small cooling capacityapplications where there isn’t adequate space for an air conditioner.www.automationdirect.comEnclosures Thermal ManagementtENC-369

For the latest prices, please check AutomationDirect.com.1-800-633-0405Enclosure Cooling –Selecting a Fan or Cooling DeviceFan selectionTo select the proper size (CFM) fan for your forced air coolingsolution, you need to determine the amount of heat to be removed(in watts) and determine the Delta T (Max. allowable internalenclosure temperature F – Max. outside ambient temperature F).CFM Cubic Feet per MinuteP Power to be dissipated in wattsCFM (3.17 x Pwatts) / Delta T FDelta T m ax. allowable internal enclosure temperature F – max.outside ambient temperature FFan Selection ExampleANEMA12WiegmannN12302412enclosure(30” high x 24” wide x 12” deep) contains a GS3-2020 ACdrive (20 HP 230 volt) that has a maximum allowable operatingtemperature of 104 F and is located in a warehouse that has amaximum outside ambient air temperature of 92 F.Power to be dissipated is stated in the specifications of theGS3-2020 and is found to be 750 watts, so P 750 wattsDelta T Max. operating temperature for the GS3-2020 is104 F – Max. ambient air temperature of 92 FDelta T 9 FCFM (3.17 x 750 watts) / 12 FCFM 198Stego offers an online Cooling Calculation Tool to help youcalculate the required airflow rate for your application.Air conditioner thermoelectric coolerand vortex cooler selectionTo select the proper size air conditioner or vortex cooler, the worstcase conditions should be considered, but take care not to choosean oversized unit.There are two main factors in choosing an uninsulated metalNEMA rated enclosure located indoors: Internal heat load Heat load transferInternal Heat LoadInternal heat load is the heat generated by the components insidethe enclosure. This can be determined by a few different methods.The preferred method is to add the maximum heat outputspecifications that the manufacturers list for all the equipmentinstalled in the cabinet. This is typically given in Watts, so use thefollowing conversion:BTU per Hour Watts x 3.413Choose a Stego 018740-30 230VAC FPI filter fan with a118740-00 exhaust grille to provide 220 CFM or a Stego018840-00 230VAC FPO filter fan with a 118840-30 intake grilleto provide 243 CFM.Air Conditioner Device Selection ExampleANEMA12WiegmannN12302412enclosure(30” high x 24” wide x 12” deep) contains a GS3-4030 ACdrive 30 HP 460 volt) that has a maximum allowable operatingtemperature of 104 F and is located in a warehouse that has amaximum outside ambient air temperature of 115 F.Power to be dissipated is stated in the specifications of theGS3-4030 and is found to be 1290 watts.Internal heat load:BTU per Hour 1290 watts x 3.413BTU per Hour 4403 BTU/HHeat load transfer:Heat load transfer (BTU/H) 1.25 x 19 sq. ft. x (115 F – 104 F)Heat load transfer (BTU/H) 261.25 BTU/HCooling capacity:Cooling capacity (BTU/H) 4403 BTU/H 261.25 BTU/HCooling capacity (BTU/H) 4664.25 BTU/HIn this example, you are able to determine that a 5000 BTU/Hunit is needed. Select a TA10-050-16-12 Stratus air conditioner.Example: The Watt-loss chart for the GS3 Drives shows that aGS3-2020 AC drive has a Watt-loss of 750 watts.Note: The same calculation method is used for sizingthermoelectric coolers and Stratus vortex coolers.However, in this example the cooling requirementsBTU per Hour 750 watts x 3.413BTU per Hour 2559exceed the maximum capacity of the largest availableHeat Load Transfervortex or thermoelectric cooler. If the exampleapplication required the use of a vortex or thermo-Heat load transfer is the heat lost (negative heat load transfer) orgained (positive heat load transfer) through the enclosure wallswith the surrounding ambient air. This can be calculated by thefollowing formula:electric cooler instead of an air conditioner, two(2) TV35-025-4X units or ten (10) 3052303 thermoelectric units would be needed.Heat load transfer (BTU/H) 1.25 x surface area (sq. ft.) x (max. outsideambient air ( F) – max. allowable internal enclosure temperature air ( F))Surface Area (sq. ft.) 2 [(H x W) (H x D) (W x D)] / 144 sq. inches Note: 1.25 is an industry standard constant for metal enclosures; 0.62should be used for plastic rOnce you have determined your Internal Heat Load and the HeatLoad Transfer, you can choose the proper size unit by calculatingthe needed cooling capacity.Cooling capacity (BTU/H) Internal Heat Load Heat Load es Thermal ManagementtENC-370

For the latest prices, please check AutomationDirect.com.1-800-633-0405Industrial strength cooling options for yourenclosure from AutomationDirect Both intake (FPI) and exhaust (FPO) fans are available. Exhaust fans and grilles available with air flaps or filters. Using airflaps on the exhaust reduces the number of filters to maintain.Filter Fan KitsFilter Fan Plus Easy filter change Outer door lock for outdoor models Impact resistant Weather/UV resistant -f1 Flammability Rating: UL94V-0 Adhesive mounting for non-screw installation(except outdoor models) Low noise 120VAC and 24VDC models available Easy filter change Hinged cover Impact resistant Weather/UV resistant-UL-f1 Flammability Rating: UL94V-0 Unique ratchet mechanism for no-screw installation Low noise 120, 230VAC and 12, 24, 48VDC models availableHose-Proof Filter Fan Hoods Stainless steel hood with food-grade silicone seal Fits all Stego Filter Fan and Filter Fan Plus fans andexhaust grilles (except outdoor Filter Fans) Maintains an enclosure’s NEMA/UL Type 4 or 4X ratingin washdown environmentsFan Kits All models are 115V with an expected service life of 30,000 hours High-performance fan motors and finger guards Polycarbonate fire retardant plastic grilles, UL94-V0 Durable, reusable filter mat included Patented “Click and Fit” system allows for rapid filter fan and exhaust filter installationwithout screwswww.automationdirect.comEnclosures Thermal ManagementtENC-371

For the latest prices, please check AutomationDirect.com.1-800-633-0405Industrial strength cooling options for yourenclosure from AutomationDirectHeat Exchangers For NEMA 4 and 4X enclosures Closed loop cooling Energy efficient: uses approximately the same power as a filtered fan system 120VAC and 24VDC models available UL Made in the USAAir Conditioning Units For NEMA 12, 4, 4X type enclosures Digital temperature controller Active condensate evaporation system High unit efficiency Tough industrial construction Compressor protection systemEnclosure Vortex Coolers For NEMA 12, 4, 4X type enclosures Operates on compressed air Stainless steel construction No moving parts, no maintenance required Vortex coolers can be “resized” for changingapplications by simply replacing the generatorinside the cooler. No need to purchase a newunit Replacing the vortex generator takesminuteswww.automationdirect.comSeifert Thermoelectric Cooling Units For NEMA 4, 4X and 12 enclosures Stainless steel housing 170, 340, 510, 680 BTU/H cooling capacity Recessed mounting No maintenance required 24VDC and 120VAC power optionsEnclosures Thermal ManagementtENC-372

For the latest prices, please check AutomationDirect.com.1-800-633-0405Filter Fan PlusAir Flap DesignThe Stego Filter Fan Plus series employs a new air flap designfor the air outlet. The air flaps have less resistance to airflowthan an exhaust filter, which allows the Filter Fan Plus systemto achieve higher airflow while still preventing the ingress ofcontaminants. Curved air flaps react to small airflow volumesfor maximum opening of flaps. Filter Fan Plus series fans arefor indoor use only.Ratchet MountingA ratchet mechanism is used for mounting, providinga high stability and tightness. No mounting screwsneeded. Prevents enclosure wall deformity whenmounting. Solid locking ensures uniform seal.Poured-in-placepolyurethanegasketwarmFilter Fan Plus Models: FPI or FPOExhaust Grille FPIAir-flapsFilter matwarmcoldFilter Fan FPIFilter Fan FPOAir-flapswww.automationdirect.comIn FPO systems (airflow direction‘out’), the filter fan is located inthe upper area of the enclosureto avoid heat buildups. The heatcan be diverted quicker fromthe critical area. An intake grillewith a filter in the lower part ofthe enclosure allows the colderair from the outside to enter.Intake Filter FPOcoldA common 3 to 3.5mm screwdriver is usedto release the ratchetmechanism.FPI systems (airflow direction‘in’) use a filter fan in thelower part of the enclosure,ensuring fresh air is fed into theenclosure. The air rises to thetop of the enclosure, coolingthe internal space and pushingthe warm interior air throughthe exhaust grille near the top.This grille exhausts hot air moreeffectively, thanks to new air flapoutlet technology.Filter matEnclosures Thermal ManagementtENC-373

For the latest prices, please check AutomationDirect.com.1-800-633-0405Filter Fan PlusFeaturesfan - 018700-30 FPI (airflow in) or FPO (airflow out) models Air flap outlet technology IP54 dust and splash waterproof Easy filter change with access provided via the hinged cover Impact resistant UV light resistant according to UL 746C (f1) Flame retardant: UL94 V-0 Low noise 115 and 230VAC models available 12, 24, and 48VDC models available (4) 6-position ratchet lever mount mechanism will accommodate wallthickness 0.039 - 0.157in (1 - 4mm)Constructionfilter - 118700-00ApplicationsFilter fans provide an optimum climate in enclosures withelectrical/electronic components. The interior temperature ofenclosures is reduced by channeling cooler filtered outside airinto the enclosure, thus expelling heated internal air. The resultingair flow prevents formation of localized heat pockets and protectselectronic components from overheating.3.62 x 3.62 inwww.automationdirect.com4.88 x 4.88 in Fan body is light gray plastic polycarbonate FPI model has an intake filter fan and an exit grille with air flaps FPO model has an exit fan with air flaps and an intake grille with filter Poured-in-place polyurethane gasket for better seal Mounts using built-in ratchet mechanism; no screws needed.(Hardware provided for optional screw mounting. Hole markings forscrew mounting are indicated on mounting frame.) Standards All models: IP54, VDE, EAC, CE, UL Type 12 when using supplied filter. UL Recognized - file: E2343246.93 x 6.93 in8.78 x 8.78 in11.46 x 11.46 inEnclosures Thermal ManagementtENC-374

For the latest prices, please check AutomationDirect.com.1-800-633-0405Filter Fan Plus3.62 x 3.62 inch Cutout Size018700-30 Storage temperature: -40 to 158 F (-40 to 70 C) Operating temperature: -4 to 158 F (-20 to 70 C) Connection type: 2 stranded wires, 11.8” (300mm) l ong, AWG 22 Service life: AC - 52,500 hrs @ 104 F (40 C)DC - 70,000 hrs @ 104 F (40 C) Average arrestance: 84% with provided G3 (coarse) filter Replacement filter matsG3 (coarse): 086330-00G4 (medium): 086270-00M5 (fine): 086300-00118700-00Filter Fan Plus - FPI scriptionAirflowFlapsVoltage sumption (W)(mA)(CFM)Airflowwith Max Static SoundGrille & Pressure LevelFilters(Pa)(dB)(CFM)Part NumberPrice018700-30 69.00Enclosure fanG3 filter230VAC1252117.74239018701-30 78.00Enclosure fanG3 filter48VDC3.06314104551018702-30 73.00Enclosure fanG3 filter24VDC2.7113139.44249018703-30 78.00Enclosure fanG3 filter12VDC2.621613104836018709-30 69.00Enclosure fanG3 filter115VAC1196149.46043118700-00 22.50Exhaust grilleAir flapsFPI exhaust grille designed to be used with the FPI fans listed above only.Note: Performance data (current draw, power consumption, free airflow with a grille and filters, sound level) for all AC fans is based on 60Hz.018800-00118800-30Filter Fan Plus - FPO SystemPart NumberFreeFilter/OperatingPowerConCurrentDrawPrice Description Air Flaps Voltage sumption (W)Airflow(mA)(CFM)AirflowMaxwithSoundStaticGrille & Pressure LevelFilters(dB)(Pa)(CFM)018800-00 72.00Enclosure fanAir flaps230VAC1252148.84238018800-40 69.00Enclosure fanG3 filter230VAC1252117.44236018801-00 81.00Enclosure fanAir flaps48VDC3.06319114149018802-00 77.00Enclosure fanAir flaps24VDC2.711318103748018803-00 81.00Enclosure fanAir 9-00 72.00Enclosure fanAir flaps115VAC11018809-40 69.00Enclosure fanG3 filter115VAC11118800-30 20.50Intake grilleG3 filterFPO intake grille designed to be used with the FPO fans listed above only.Note: Performance data (current draw, power consumption, free airflow with a grille and filters, sound level) for all AC fans is based on 60Hz.See our website: www.AutomationDirect.com for complete engineering drawingswww.automationdirect.comEnclosures Thermal ManagementtENC-375

For the latest prices, please check AutomationDirect.com.1-800-633-0405Filter Fan Plus4.88 x 4.88 inch Cutout Size018710-30 Storage temperature: -40 to 158 F (-40 to 70 C) Operating temperature: -4 to 158 F (-20 to 70 C) Connection type: 2 stranded wires, 11.8” (300mm) l ong, AWG 22 Service life: AC - 37,500 hrs @ 104 F (40 C)DC - 65,000 hrs @ 104 F (40 C) Average arrestance: 84% with provided G3 (coarse) filter Replacement filter matsG3 (coarse): 086340-00G4 (medium): 086010-00M5 (fine): 086040-00118710-00Filter Fan Plus - FPI SystemFreeAir Operating Power ConCurrentDescription Filter/AirflowFlapsVoltage sumption (W) Draw (mA)(CFM)Part NumberPrice018710-30 75.00Enclosure fanG3 filter230VAC19018711-30 85.00Enclosure fanG3 filter48VDC018712-30 80.00Enclosure fanG3 filter24VDC018713-30 85.00Enclosure fanG3 filter018719-30 75.00Enclosure fanG3 filter118710-00 26.00Exhaust grilleAir flapsAirflowwith Max Static SoundGrille & Pressure FPI exhaust grille designed to be used with the FPI fans listed above only.Note: Performance data (current draw, power consumption, free airflow with a grille and filters, sound level) for all AC fans is based on 60Hz.018810-00118810-30Filter Fan Plus - FPO SystemPart NumberPrice DescriptionFilter/Air FlapsFreeOperating Power Con- Current Draw AirflowVoltage sumption (W)(mA)(CFM)AirflowMaxwithSoundStaticGrille & Pressure LevelFilters(dB)(Pa)(CFM)018810-00 79.00Enclosure fanAir flaps230VAC198357287549018810-40 79.00Enclosure fanG3 filter230VAC198332226442018811-00 88.00Enclosure fanAir flaps48VDC4.28874379250018812-00 84.00Enclosure fanAir flaps24VDC4.518870378856018813-00 88.00Enclosure fanAir flaps12VDC4.537570368842018819-00 79.00Enclosure fanAir flaps115VAC1815769348252018819-40 75.00Enclosure fanG3 filter115VAC1815739287042118810-30 23.50Intake grilleG3 filterFPO intake grille designed to be used with the FPO fans listed above only.Note: Performance data (current draw, power consumption, free airflow with a grille and filters, sound level) for all AC fans is based on 60Hz.www.automationdirect.comEnclosures Thermal ManagementtENC-377

For the latest prices, please check AutomationDirect.com.1-800-633-0405Filter Fan Plus6.93 x 6.93 inch Cutout Size018720-30 Storage temperature: -40 to 158 F (-40 to 70 C) Operating temperature: -13 to 158 F (-25 to 70 C) Connection type: 3-pole clamp for AWG 14 (2.5 mm2), screw clamptorque 7.1 lb·in (0.8 N·m) max Service life: AC - 65,000 hrs @ 104 F (40 C)DC - 80,000 hrs @ 104 F (40 C) Average arrestance: 84% with provided G3 (coarse) filter Replacement filter matsG3 (coarse): 086350-00G4 (medium): 086020-00M5 (fine): 086050-00118720-00Filter Fan Plus - FPI SystemPart NumberFreeFilter/OperatingPowerConCurrentDrawPrice Description Air Flaps Voltage sumption (W)Airflow(mA)(CFM)Airflowwith Max Static SoundGrille & Pressure LevelFilters(Pa)(dB)(CFM)018720-30 129.00Enclosure fanG3 filter230VAC451961008212155018721-30 190.00Enclosure fanG3 filter48VDC122501008712263018722-30 190.00Enclosure fanG3 filter24VDC125001059212563018723-30 190.00Enclosure fanG3 filter12VDC1210001068812753018729-30 144.00Enclosure fanG3 filter115VAC3833012011012158118720-00 35.50Exhaust grilleAir flapsFPI exhaust grille designed to be used with the FPI fans listed above only.Note: Performance data (current draw, power consumption, free airflow with a grille and filters, sound level) for all AC fans is based on 60Hz.018820-00118820-30Filter Fan Plus - FPO SystemPart NumberFilter/Operating Power Con- Current DrawPrice Description AirFlaps Voltage sumption (W)(mA)FreeAirflow(CFM)AirflowMaxwithStatic SoundGrille & PressureLevelFilters(dB)(Pa)(CFM)018820-00 136.00Enclosure fanAir flaps230VAC451961558114356018820-40 136.00Enclosure fanG3 filter230VAC451961067112153018821-00 199.00Enclosure fanAir flaps48VDC122501638614663018822-00 199.00Enclosure fanAir flaps24VDC125001598313863018823-00 199.00Enclosure fanAir flaps12VDC1210001648215053018829-00 151.00Enclosure fanAir flaps115VAC383301849816260018829-40 144.00Enclosure fanG3 filter115VAC383301268713953118820-30 27.50Intake grilleG3 filterFPO intake grille designed to be used with the FPO fans listed above only.Note: Performance data (current draw, power consumption, free airflow with a grille and filters, sound level) for all AC fans is based on 60Hz.www.automationdirect.comEnclosures Thermal ManagementtENC-379

For the latest prices, please check AutomationDirect.com.1-800-633-0405Filter Fan Plus8.78 x 8.78 inch Cutout Size018730-30 Storage temperature: -40 to 158 F (-40 to 70 C) Operating temperature: -13 to 149 F (-25 to 65 C) Connection type: 3-pole clamp for AWG 14 (2.5 mm2), clampingtorque 7.1 lb·in (0.8 N·m) max Service life: 56,000 hrs @ 104 F (40 C) Average arrestance: 84% with provided G3 (coarse) filter Replacement filter matsG3 (coarse): 086360-00G4 (medium):086280-00M5 (fine): 086310-00118730-00Filter Fan Plus - FPI SystemPart NumberPrice DescriptionFilter/Air FlapsFreeOperating Power Con- Current Draw AirflowVoltage sumption (W)(mA)(CFM)Airflowwith Max Static SoundGrille & Pressure LevelFilters(Pa)(dB)(CFM)018730-30 165.00Enclosure fanG3 filter230VAC6427818016015464018739-30 173.00Enclosure fanG3 filter115VAC817041951739267118730-00 47.00Exhaust grilleAir flapsFPI exhaust grille designed to be used with the FPI fans listed above only.Note: Performance data (current draw, power consumption, free airflow with a grille and filters, sound level) for all AC fans is based on 60Hz.018830-00118830-30Filter Fan Plus - FPO SystemPart NumberPrice DescriptionFilter/Air FlapsFreeOperating Power Con- Current Draw AirflowVoltage sumption (W)(mA)(CFM)AirflowMaxwithSoundStaticGrille & Pressure LevelFilters(dB)(Pa)(CFM)018830-00 177.00Enclosure fanAir flaps230VAC6427831616517265018830-40 165.00Enclosure fanG3 filter230VAC6427817713415465018839-00 195.00Enclosure fanAir 8839-40 173.00Enclosure fanG3 filter118830-30 33.50Intake grilleG3 filterFPO intake grille designed to be used with the FPO fans listed above only.Note: Performance data (current draw, power consumption, free airflow with a grille and filters, sound level) for all AC fans is based on 60Hz.www.automationdirect.comEnclosures Thermal ManagementtENC-381

1-800-633-0405For the latest prices, please check AutomationDirect.com.Filter Fan Plus11.46 x 11.46 inch Cutout Size018740-30 Storage temperature: -40 to 158 F (-40 to 70 C) Operating temperature: -13 to 95 F (-25 to 35 C) Connection type: 3-pole clamp for AWG 14 (2.5 mm2), clampingtorque 7.1 lb·in (0.8 N·m) max Service life: 76,000 hrs @ 104 F (40 C) Average arrestance: 84% with provided G3 (coarse) filter Replacement filter matsG3 (coarse): 086370-00G4 (medium):086290-00M5 (fine): 086320-00118740-00Filter Fan Plus - FPI SystemOperating Power ConVoltage sumption (W)CurrentDraw(mA)FreeAirflow(CFM)Airflowwith Max Static SoundGrille & Pressure LevelFilters(Pa)(dB)(CFM)Part NumberPriceDescriptionFilter/Air Flaps018740-30 222.00Enclosure fanG3 filter230VAC954132552209962018740-31 254.00Enclosure fanG3 filter230VAC14070036733011270018749-30 241.00Enclosure fanG3 filter115VAC907832322007361018749-31 270.00Enclosure fanG3 filter115VAC165145039134913572118740-00 71.00Exhaust grilleAir flapsFPI exhaust grille designed to be used with the FPI fans listed above only.Note: Performance data (current draw, power consumption, free airflow with a grille and filters, sound level) for all AC fans is based on 60Hz.118840-30018840-00Filter Fan Plus - FPO SystemPart NumberPrice DescriptionFilter/Air FlapsFreeOperating Power ConCurrent AirflowVoltage sumption (W) Draw (mA)(CFM)AirflowMaxwithStatic SoundGrille & PressureLevelFilters(dB)(Pa)(CFM)018840-00 234.00Enclosure fanAir flaps230VAC9541342824310763018840-01 266.00Enclosure fanAir flaps230VAC1407003953537070018840-40 222.00Enclosure fanG3 filter230VAC954132651879963018849-00 253.00Enclosure fanAir flaps115VAC907834142308062018849-01 282.00Enclosure fanAir flaps115VAC16514506073599071018849-40 241.00Enclosure fanG3 filter115VAC907832561777362118840-30 55.00Intake grilleG3 filterFPO intake grille designed to be used with the FPO fans listed above only.Note: Performance data (current draw, power consumption, free airflow with a grille and filters, sound level) for all AC fans is based on 60Hz.www.automationdirect.comEnclosures Thermal ManagementtENC-383

For the latest prices, please check AutomationDirect.com.1-800-633-0405Filter FanApplications018000-02Features Easy filter change Outer door lock for outdoor models Impact resistant Weather/UV resistant UL-f1 Flammability Rating: UL 94V-0 No-screw installation - except outdoor models Low noise 120VAC and 24VDC models available Service life - 50,000 [email protected] F (25 C) 65%RH Connection type - 12 to 69 CFM - 2 wires w/case clamps, AWG 14,length 4”/136 to 373 CFM - 3 pole terminal, AWG 14, clamping torque0.8 N·m Airflow direction easily switched by reversing the axial fan (except onmodels 018040-01 and 018050-01) Includes self-adhesive gasket pre-installed on frame Optional mounting screws for additional support G3 (coarse), G4 (medium) and M5 (fine) replacement filter matsavailableFilter fans provide an optimumclimate in enclosures. T

A typical forced convection system consists of a fan and a grille, with a filter on the intake device and either a filter or louvers on the exhaust device. The filters and louvers allow the enclosure to maintain NEMA 12 protection. In NEMA 4 or NEMA 4X environments, hoods can be added to both the fan and the grille to prevent the ingress of water.